APG 33

Product: PSI Alternator: ECP 28-VL/4 C CONTROL SYSTEM: DSE 6120
INTRODUCTION

Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.

General Characteristics
Model Name APG 33
Frequency (Hz) 50
Fuel Type Natural Gas
Engine Made and Model PSI - 4.3L (4X)_ APG33
Alternator Made and Model Mecc Alte - ECP 28-VL/4 C
Control Panel Model DSE 6120
Canopy AUL3
3 Phase, 50 Hz, PF 0.8
VOLTAGE STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 33 26.40 30 24.00 47.63
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine PSI
Engine Model 4.3L (4X)_ APG33
NO. OF CYLINDERS AND BUILD 6 cylinders - V type
BORE AND STROKE mm 101,6 (4) X 88 (3.5)
TOTAL DISPLACEMENT L 4,3 (262)
Aspiration Naturally Aspirated
COMPRESSION RATIO 9.8:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 4,3 (1,1)
Standby Power (kW/HP) 48,2 (64,7)
Prime Power 43,4 (58,2)
Block Heater QTY
1
Block Heater Power (Watt)
500
Fuel Type
Natural Gas
Injection Type and System
Spark-Ignited
Type of Fuel Pump
-
Governor System
ECU
Operating Voltage (Vdc)
12 Vdc
Battery and Capacity (Qty/Ah)
1 / 55
Cooling Method
Water Cooled
Coolant Capacity (engine only) (l)
7,3 (1,93)
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (m3/hr)
9,3 (6,7) (standby)
ALTERNATOR SPECIFICATIONS
Manufacturer Mecc Alte
Alternator Made and Model ECP 28-VL/4 C
Frequency (Hz) Hz 50
Power (kVA) kVA 30
DESIGN   4 Pole,  Brushless
VOLTAGE V 400
Phase 3
A.V.R. DSR
Voltage Regulation (+/-) 1
Insulation System H
Protection IP23
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 141.8
COOLING AIR (m³/min) m3 6.6
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
2278 (7,5) 1063 (3,5) 1404 (4,6)
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
AUL3
2274 (90) 1062 (42) 1307 (52)
STANDARD SPECIFICATIONS

- Water cooled, gas engine

- Radiator with mechanical fan

- Protective grille for rotating and hot parts

- Electric starter and charge alternator

- Starting battery (with lead acid) including rack and cables

- Engine coolant heater

- Base frame design incorporates an anti-vibration isolators

- Flexible fuel connection hoses

- Single bearing, class H alternator

- Industrial exhaust silencer and steel bellows supplied separately(for open sets)

- Static battery charger

- Manual for application and installation

CONTROL SYSTEM: DSE 6120
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Devices

DSE model 6120, Auto Mains Failure control module, Static battery charger input 198-264 volt, output 27,6V 5A (24V) or

13,8 Volt 5A (12V), fuses for control circuits. This Control Module is suitable for a wide variety of single gen-set applications

CONSTRUCTION and FINISH

Components installed in sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion corrosion-resistant surface. Polyester composite powder topcoat forms a high gloss and extremely durable finish. Lockable and hinged panel door provides easy access to components.

INSTALLATION

Control panel is mounted on baseframe with steel stand. Located at the right side of the generator set (When you look at the Gen.Set. from Alternator side)

GENERATING SET CONTROL UNIT

- The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant

temperature running hours and battery volts.

- Module monitors the mains supply and control the switch over to the generator when the mains power fails.

- The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving

true first up fault condition of Gen. Set failure.The LCD display indicates the fault.


Instruments
ENGINE
●Engine speed.
●Oil pressure.
●Coolant temperature.
●Run time.
●Battery volts.
●Configurable timing.

GENERATOR
●Voltage (L-L, L-N).
●Current (L1-L2-L3).
●Frequency.
●Gen. Set ready.
●Gen. Set enabled.

MAINS
●Mains ready.
●Mains enabled.

Options

- Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)

- Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).

Standards

- Electrical Safety / Electro Magenetic Compatibility (EMC)

- BS EN 60950 Electrical Safety

- BS EN 61000-6-2 EMC Generic Immunity Standard

- BS EN 61000-6-4 EMC Generic Emission Standard

STATIC BATTERY CHARGER

- Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.

- Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and

27,6 V for 24 V . Input 198 - 264 volt AC.

- The charger is fitted with a protection diode across the output.

- Connect charge fail relay coil between positive output and CF output.

- They are equipped with RFI filter to reduce electrical noise radiated from the device.

- Galvanically isolated input and output typically 4kV for high reliability.

Canopy: AUL3
STANDARD SPECIFICATIONS


CANOPY MODEL AUL3
WIDTH mm. 1062 (42)
LENGTH mm. 2274 (90)
HEIGHT mm. 1307 (52)
TANK CAPACITY (lt.) Lt.