APD 88 BD

Product: BAUDOUIN Alternator: AK 370 CONTROL SYSTEM: DSE 6120
INTRODUCTION
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
Certificate
  TS ISO 8528
  CE
  SZUTEST
  2000/14/EC
General Characteristics
Model Name APD 88 BD
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model BAUDOUIN - 4M10G4D0
Alternator Made and Model Aksa - AK 370
Control Panel Model DSE 6120
Canopy ACP 6A
3 Phase, 50 Hz, PF 0.8
VOLTAGE STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 88 70.40 80 64.00 127.02
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine BAUDOUIN
Engine Model 4M10G4D0
NO. OF CYLINDERS AND BUILD 4 cylinders - in line
BORE AND STROKE mm 105 X 118
TOTAL DISPLACEMENT L 4.087
Aspiration Turbo Charged
COMPRESSION RATIO 17.5:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 13
Standby Power (kW/HP) 80/107
Prime Power 72/97
Block Heater QTY
1
Block Heater Power (Watt)
1000
Fuel Type
Diesel
Injection Type and System
Direct
Type of Fuel Pump
Mechanical
Governor System
Electronic
Operating Voltage (Vdc)
12 Vdc
Battery and Capacity (Qty/Ah)
1x66
Charge Alternator (A)
55
Cooling Method
Water Cooled
Cooling Fan Air Flow (m3/min)
146
Coolant Capacity (engine only) (l)
9.4/17.9
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (lt/hr)
18.8
Fuel Cons. Prime With %75 Load (lt/hr)
13.5
Fuel Cons. Prime With %50 Load (lt/hr)
9.1
ALTERNATOR SPECIFICATIONS
Manufacturer Aksa
Alternator Made and Model AK 370
Frequency (Hz) Hz 50
Power (kVA) kVA 87,5
DESIGN   Brushless
VOLTAGE V 400
Phase 3
A.V.R. SX460
Voltage Regulation (+/-) 1,5%
Insulation System H
Protection IP22
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 383
COOLING AIR (m³/min) m3 12,96
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
1165 2348 1004 1275 180
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
ACP 6A
1415 2600 1058 1590 180
STANDARD SPECIFICATIONS
Water cooled, Diesel engine 
Radiator with mechanical fan 
Protective grille for rotating and hot parts 
Electric starter and charge alternator 
Starting battery (with lead acid) including rack and cables 
Engine coolant heater 
Base frame design incorporates an integral fuel tank and anti-vibration isolators 
Flexible fuel connection hoses 
Single bearing, class H alternator 
Industrial exhaust silencer and steel bellows supplied separately(for open sets) 
Static battery charger 
Manual for application and installation
OPTIONAL EQUIPMENTS
ENGINE
• Fuel-Water Seperator Filter
• Oil heater

ALTERNATOR
• Anti-Condensation Heater
• Over sized alternator
• PMG excitation + AVR
• Main line circuit breaker
CONTROL SYSTEM
• Automatic synchronising and power control system ( multi gen-set Parallel )
• Transition synchronization with mains
• Remote annunciator panel
• Remote relay output
• Alarm output relays
• Remote communication with modem
• Earth fault, single set
• Charge Ammeter

TRANSFER SWITCH
• Three Pole Contactor
• Four Pole Contactor
• Three or four pole motor operated circuit breaker

OTHER ACCESSORIES
• Main Fuel Tank
• Automatic or manual fuel filling system
• Manual oil drain pump
• Electrical oil drain pump
• Low and high fuel level alarm
• Residential silencer
• Enclosure: weater protective or sound attenuated
• Duct adapter ( on radiator)
• Inlet and outlet motorised louvers
• Inlet and outlet acoustic baffles
• Trailer
• Tool kit for maintenance
• Automatic transfer switch
CONTROL SYSTEM: DSE 6120
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Devices
●DSE, model 6120 Auto Mains Failure control module.
●Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V)
●Emergency stop push button and fuses for control circuits.
CONSTRUCTION and FINISH
●Components installed in a sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion resistant surface. Polyester composite powder topcoat forms high gloss and an extremely durable finish. Lockable and hinged panel door provides easy access to components.
INSTALLATION
Control panel is mounted on baseframe with a steel stand. Located at the right side of the generator set (When you look at the Gen.Set. from Alternator)
GENERATING SET CONTROL UNIT
The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant temperature running hours and battery volts.
Module monitors the mains supply and switches over to the generator when the mains power fails.
The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving true first-up fault condition of Gen. Set failure.The LCD display indicates the fault.
STANDARD SPECIFICATIONS
●Microprocessor controlled.
●LCD display makes information easy to read.
●Automatically transfers between mains (utility) and generator power.
●Manual programming on the front panel.
●User-friendly set-up and button layout.
●Remote start.
●Event logging (50) showing date and time.
●Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to scroll through the modules' metering displays.
Instruments
ENGINE
●Engine speed.
●Oil pressure.
●Coolant temperature.
●Run time.
●Battery volts.
●Configurable timing.

GENERATOR
●Voltage (L-L, L-N).
●Current (L1-L2-L3).
●Frequency.
●Gen. Set ready.
●Gen. Set enabled.

MAINS
●Mains ready.
●Mains enabled.
Protection Circuits
WARNING 
●Charge failure. 
●Battery Low/High voltage. 
●Fail to stop. 
●Low /High generator voltage. 
●Under /Over generator frequency. 
●Over /Under speed. 
●Low oil pressure. 
●High coolant temperature. 

SHUTDOWNS 
●Fail to start.
●Emergency stop. 
●Low oil pressure. 
●High coolant temperature. 
●Over /Under speed. 
●Under/over generator frequency. 
●Under/over generator voltage. 
●Oil pressure sensor open. 
●Coolant temperature sensor open. 

ELECTRICAL TRIP 
●Generator over current.

Options
●Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)
●Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).
Standards
●Elecrical Safety / EMC compatibility
●BS EN 60950 Electrical business equipment.
●BS EN 61000-6-2 EMC immunity standard.
●BS EN 61000-6-4 EMC emission standard
STATIC BATTERY CHARGER
● Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.
● Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volts and 27,6 V for 24 V . Input 198 - 264 volt AC.
● The charger is fitted with a protection diode across the output.
● Connect charge fail relay coil between the positive output and CF output.
● They are equipped with RFI filter to reduce electrical noise radiated from the device.
● Galvanically isolated input and output typically 4kV for high reliability.
Canopy: ACP 6A
1. Steel structures. 
2. Emergency stop push button. 
3. Control panel is mounted on the baseframe . Located at the right side of the generator set. 
4. Corrosion-resistant locks and hinges. 
5. Oil could be drained via valve and a hose 
6. Exhaust system in the canopy. 
7. Special large access doors for easy maintanance 
8. In front and back side special large access doors for easy maintanance 
9. Base frame -fuel tank. 
11. The cap on the canopy provides easy accsess to radiator cap. 
12. Sound proofing materials 
13. Plastic air intake pockets.
INTRODUCTION
Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
STANDARD SPECIFICATIONS
Compact footprint, low profile design.
Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package
Body made from steel components treated with polyester powder coating
Fire retardant foam insulation
Easy access to all service points
Exhaust system inside canopy
Large doors on each side
Control panel viewing window in a lockable access door
Emergency stop push button mounted on enclosure exterior
Cooling fan and battery charging alternator fully guarded
Fuel fill and battery can only be reached via lockable access doors.
Lifting points on the top of canopy and base frame
Customer options available to meet your applications needs.
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest

CANOPY MODEL ACP 6A
WIDTH mm. 1058
LENGTH mm. 2600
HEIGHT mm. 1590
TANK CAPACITY (lt.) Lt. 180